Home  |   About Us   |   Products   |   Market   |   News  |   Feedback   |   Contact Us
 
 
   Refrigerant Gas
Manifolds Gauge
Refrigeration Oil
Generator
Vacuum Pump
Valves
Copper/Steel Tube
Cylinders/Tanks
Air-Conditioners
Chemicals
 
  Home >>MSDS>> Content
  R143A MSDS
 
 
MATERIAL SAFETY DATA SHEET
R143A
 
1 IDENTIFICATION OF THE SUBSTANCE / PREPARATION AND OF THE COMPANY / UNDERTAKING
Trade name : Trifluoroethane (R143a)
MSDS No : AL118
Chemical formula : C2H3F3
Company identification : AIR LIQUIDE SA
 
Company: BEST INC., LIMITED.
Add.: Rooms 1318-20, 13/F Hollywood Plaza, 610 Nathan Road, Mongkok, Kowloon, Hong Kong
Tel: +852-30774337       Fax:+852-30774338
 
2 COMPOSITION / INFORMATION ON INGREDIENTS
Substance / Preparation : Substance.
Substance name        Contents   CAS No    EC No     Index No    Classification
Trifluoroethane (R143a) : 100 %    420-46-2   206-996-5                F+; R12
Contains no other components or impurities which will influence the classification of the product.
 
3 HAZARDS IDENTIFICATION
Hazards identification : Liquefied gas.
Extremely flammable.
 
4 FIRST AID MEASURES
First aid measures
-Inhalation : In high concentrations may cause asphyxiation. Symptoms may include loss of
mobility/consciousness. Victim may not be aware of asphyxiation.
In low concentrations may cause narcotic effects. Symptoms may include dizziness, headache, nausea and loss of co-ordination.
Remove victim to uncontaminated area wearing self contained breathing apparatus. Keep victim warm and rested. Call a doctor. Apply artificial respiration if breathing stopped.
- Skin/eye contact : For liquid spillage - flush with water for at least 15 minutes.
-Ingestion : Ingestion is not considered a potential route of exposure.
 
5 FIRE-FIGHTING MEASURES
Flammable class : Extremely flammable.
Specific hazards : Exposure to fire may cause containers to rupture/explode.
Hazardous combustion products : If involved in a fire the following toxic and/or corrosive fumes may be produced by thermal decomposition :
Carbonyl fluoride.
Carbon monoxide.
Hydrogen fluoride.
 
Extinguishing media
-Suitable extinguishing media : All known extinguishants can be used.
Specific methods : If possible, stop flow of product.
Move away from the container and cool with water from a protected position.
Do not extinguish a leaking gas flame unless absolutely necessary. Spontaneous/
explosive re-ignition may occur. Extinguish any other fire.
Special protective equipment for fire fighters: Use self-contained breathing apparatus and chemically protective clothing.
 
 
6 ACCIDENTAL RELEASE MEASURES
Personal precautions : Wear self-contained breathing apparatus when entering area unless atmosphere is proved to be safe.
Evacuate area.
Ensure adequate air ventilation.
Eliminate ignition sources.
 
Environmental precautions : Try to stop release.
Prevent from entering sewers, basements and workpits, or any place where its accumulation can be dangerous.
 
Clean up methods : Ventilate area.
 
7 HANDLING AND STORAGE
Storage : Segregate from oxidant gases and other oxidants in store.
Keep container below 50°C in a well ventilated place.
 
Handling : Ensure equipment is adequately earthed.
 
Suck back of water into the container must be prevented.
Purge air from system before introducing gas.
Do not allow backfeed into the container.
Use only properly specified equipment which is suitable for this product, its supply pressure and temperature. Contact your gas supplier if in doubt.
Keep away from ignition sources (including static discharges).
Refer to supplier's container handling instructions.
 
8 EXPOSURE CONTROLS / PERSONAL PROTECTION
Personal protection : Ensure adequate ventilation.
Do not smoke while handling product.
 
9 PHYSICAL AND CHEMICAL PROPERTIES
Physical state at 20 °C : Liquefied gas.
Colour : Colourless gas.
Odo(u)r : Sweetish. Poor warning properties at low concentrations.
Molecular weight :84
Melting point [°C] : -111
Boiling point [°C] : -47.6
Critical temperature [°C] :73
Vapour pressure, 20°C : 11.1 bar
Relative density, gas (air=1) :2.9
Relative density, liquid (water=1) :1.2
Solubility in water [mg/l] : No reliable data available.
Flammability range [vol% in air] : 9.5 to 19
Auto-ignition temperature [°C] : Not known.
Other data : Gas/vapour heavier than air. May accumulate in confined spaces, particularly at or below ground level.
 
10 STABILITY AND REACTIVITY
Stability and reactivity : Can form explosive mixture with air.
Thermal decomposition yields toxic products which can be corrosive in the presence of moisture.
May react violently with oxidants.
 
11 TOXICOLOGICAL INFORMATION
Toxicity information : No known toxicological effects from this product.
 
12 ECOLOGICAL INFORMATION
Ecological effects information : Not covered by the 'Montreal Protocol'.
Global warming factor [CO2=1] : 3800
 
13 DISPOSAL CONSIDERATIONS
General : Do not discharge into areas where there is a risk of forming an explosive mixture
with air. Waste gas should be flared through a suitable burner with flash back
arrestor.
Toxic and corrosive gases formed during combustion should be scrubbed before
discharge to atmosphere.
Do not discharge into any place where its accumulation could be dangerous.
Contact supplier if guidance is required.
 
14 TRANSPORT INFORMATION
UN No. : 2035
H.I. nr :23
ADR/RID
-Proper shipping name : 1,1,1-TRIFLUOROETHANE (REFRIGERANT GAS R 143A)
- ADR Class :2
- ADR/RID Classification code :2 F
-Labelling ADR : Label 2.1 : flammable gas.
Other transport information : Avoid transport on vehicles where the load space is not separated from the driver's compartment.
Ensure vehicle driver is aware of the potential hazards of the load and knows what to do in the event of an accident or an emergency.
Before transporting product containers :
- Ensure that containers are firmly secured.
- Ensure cylinder valve is closed and not leaking.
- Ensure valve outlet cap nut or plug (where provided) is correctly fitted.
- Ensure valve protection device (where provided) is correctly fitted.
- Ensure there is adequate ventilation.
- Compliance with applicable regulations.
 
15 REGULATORY INFORMATION
EC Classification : Not included in Annex I.
Proposed by the industry.
F+; R12
 
EC Labelling
- Symbol(s) : F+ : Extremely flammable
- R Phrase(s) : R12 : Extremely flammable.
- S Phrase(s) : S9 : Keep container in a well-ventilated place.
S16 : Keep away from sources of ignition - No smoking.
S33 : Take precautionary measures against static discharges.
 
16 OTHER INFORMATION
Ensure all national/local regulations are observed.
Ensure operators understand the flammability hazard.
Contact with liquid may cause cold burns/frostbite.
The hazard of asphyxiation is often overlooked and must be stressed during operator training.
This Safety Data Sheet has been established in accordance with the applicable European Directives and applies to all countries that have translated the Directives in their national laws.
Before using this product in any new process or experiment, a thorough material compatibility and safety study should be carried out.
Details given in this document are believed to be correct at the time of going to press. Whilst proper care has been taken in the preparation of this document, no liability for injury or damage resulting from its use can be accepted.
Recommended uses and restrictions : This SDS is for information purposes only and is subject to change without notice. [ Prior to purchase of products, please contact your local AIR LIQUIDE office for a complete SDS (with Manufacturer's name and emergency phone number).]
 
 
 
Copyright © BEST INC., LIMITED All rights reserved